KYN28-12 Metal-Clad, Center-Position, Withdrawable Switchgear
+
  • KYN28-12 Metal-Clad, Center-Position, Withdrawable Switchgear

KYN28-12 Metal-Clad, Center-Position, Withdrawable Switchgear


• The cabinet is fully assembled, making installation and maintenance convenient. • The operation is intuitive and simple, effectively reducing the likelihood of operator errors. • Fixed installation provides ample space and excellent heat dissipation.

Scope of application

The KYN28-12 type (GZS1) indoor metal-clad, center-mounted withdrawable switchgear (hereinafter referred to as the switchgear) is a three-phase, 50 Hz AC indoor complete switchgear assembly designed for receiving and distributing electrical energy in networks ranging from 3 to 12 kV, as well as for controlling, protecting, and monitoring circuit operations. On the relay compartment panel of this product, various types of microprocessor-based integrated relay protection devices can be installed, enabling intelligent system control with remote control, remote measurement, remote signaling, and remote adjustment functions. The system is controlled via a CAN bus equipped with communication interfaces, allowing it to network field devices. Moreover, the switchgear features “five-protection” functions, which prevent erroneous operations such as incorrect breaker switching, unauthorized pushing or pulling of hand carts under load, closing of grounding switches while live, energizing the grounding switch when it is in the grounded position, and unauthorized entry into live compartments. This switchgear can be equipped with either VS1 (i.e., ZN63) or ZN12V vacuum circuit breakers, or alternatively, with imported VD4 vacuum circuit breakers paired with VC-series vacuum contactors.

 

Model and Meaning

 

Operating environment conditions

● Ambient air temperature: Upper limit +40℃, lower limit -10℃ in most regions;

● Altitude: 1000m;

● Humidity:

Relative humidity: The daily average shall not exceed 95%, and the monthly average shall not exceed 90%.

Water vapor pressure: The daily average shall not exceed 2.2 kPa, and the monthly average shall not exceed 1.8 kPa. Condensation may occur when the temperature drops suddenly, accompanied by contamination. This product is suitable for the following two environmental conditions that are more severe than normal conditions:

(1) Dew formation is infrequent (averaging no more than twice per month) and there is slight contamination.

(2) Condensation generally does not occur (averaging no more than twice per year), but there is relatively severe contamination.

● Locations free from fire hazards, explosion risks, and corrosive gases or other harsh conditions that could severely damage metals and compromise insulation;

● Locations without severe vibrations, bumps, or vertical tilts exceeding 8°;

Note: (1) Storage and transportation are permitted at -30℃;

(2) For areas with an altitude exceeding 1000 m, refer to JB/2102 “Technical Requirements for High-Voltage Electrical Equipment Used in Areas at Different Altitudes.” When the altitude does not exceed 2000 m, no special measures are required for low-voltage auxiliary equipment.

(3) When the actual operating conditions differ from those described above, the user and the manufacturer shall negotiate and reach an agreement.

 

Switchgear structure

Figure 1 Figure 2: Schematic Diagram of Switchgear Structure
A. Circuit breaker compartment
B. Busbar Compartment
C. Cable Room
D. Relay Instrument Room
1. Busbar
2. Static contact box
3. Circuit breaker
4. Grounding switch
5. Current transformer
6. Capacitive Voltage Divider
7. Surge arrester
1. Shell
2. Branch busbar
3. Busbar bushing
4. Main busbar
5. Static Contact Assembly
6. Static contact box
7. Current transformer
8. Grounding switch
9. Cable
10. Surge arrester
11. Grounding main busbar
12. Detachable partition
13. Partition (flap)
14. Secondary plug
15. Circuit breaker trolley
16. Heater device
17. Removable horizontal partition
18. Grounding switch operating mechanism
19. Base plate
A. Busbar Room
B. Circuit Breaker Handcart Compartment
C. Cable Room
D. Relay Instrument Room
1.1 Pressure relief device
1.2 Control the small cable tray

Keywords: KYN28-12 Metal-Clad, Center-Position, Withdrawable Switchgear