Product Specifications:

Table

Parameter item

Standard value

Rated operating voltage

400V/690V; Insulation voltage 1000V

Rated busbar current

630–6300A

Rated short-time withstand current

25 kA, 31.5 kA, 40 kA, 50 kA (1 s)

Modular system

25 mm standard module, minimum 1/4 drawer unit

Protection rating

IP40 (indoor), IP54 (enhanced sealing)

Cabinet dimensions

Width: 400/600/800/1000 mm; Depth: 600 mm (single-sided access) / 1000 mm (double-sided); Height: 2200 mm.

Structural form

Fully assembled galvanized‑aluminum‑zinc sheet frame, with busbar compartmentalization and isolation.

 

 

Application scenarios:

  1. Power Plant and Substation : Plant auxiliary power, low-voltage distribution at the step-up substation, and substations 0.4 kV Incoming line, power distribution, reactive power compensation system ABB
  2. Heavy chemical industry : Petroleum, chemical, metallurgical, coal mining, and paper mills, serving as the motor control center ( MCC ) and the main power distribution cabinet.
  3. New energy sector : Low-voltage grid connection for photovoltaic power plants, wind farms, and energy storage stations; in-cabin power distribution; and inverter-side power distribution and control.
  4. Large-scale public infrastructure projects : Low-voltage main distribution rooms in data centers, airports, high-speed railway stations, hospitals, commercial complexes, and high-rise buildings.
  5. Industrial park supporting facilities : Power supply for various manufacturing plant workshops, centralized control of pump and fan motors, and reactive power compensation switchgear cabinets for the plant area.
  6. Special Scenarios : Offshore platforms, ships, and low-voltage distribution equipment for nuclear power plants (marine‑grade versions available with classification society certification)

 

Product Advantages:

  1. Fully modular assembly, with flexible solutions.   With 25mm To ensure modular standardization, over 200 types of standard components can be freely combined; drawers, fixed compartments, and frame‑type circuit breaker units can be mixed and matched, allowing for future expansion or upgrades without the need to replace the entire cabinet. Hangzhou Haixing Electric ...
  2. Five chambers are independently sealed, ensuring a high level of security.   The cabinet body is divided into Main busbar compartment, vertical busbar compartment, functional unit compartment, cable compartment, and instrument secondary compartment All-metal isolation and a built-in arc‑fault pressure‑relief mechanism prevent fault propagation; the drawer features an integral mechanical interlock to prohibit live insertion/removal and inadvertent closing.
  3. The drawers are interchangeable, ensuring high operational efficiency.   Drawers of the same specification are fully interchangeable; faulty circuits can be directly removed and replaced with spare drawers, significantly reducing outage‑related maintenance time. The unit features a three‑position visual lock and supports secondary circuit testing while energized.
  4. The busbar system is stable and durable.   The busbar is enclosed in an insulating sheath, features a bolt‑type self‑locking anti‑loosening mechanism, and incorporates eddy‑current‑mitigation design in high‑current sections, ensuring low temperature rise, maintenance‑free long‑term operation, and robust short‑time withstand capability.
  5. The cabinet features high structural strength and optional protection. C High-strength profile frame with excellent seismic performance; IP54 The protective design is suitable for harsh operating conditions inside outdoor pad-mounted substations, as well as in humid, dust‑laden workshops.
  6. High integration, saving floor space.   The cabinet features a compact structure, allowing a single unit to accommodate a high density of power distribution circuits. Compared with traditional fixed cabinets, it significantly reduces space requirements. 30% Left and right, it can integrate power distribution, motor control, and capacitor compensation into a unified layout.

Keywords: MNS